Data Center DirectAire Airflow Panel

DirectAire®

Cool the same load with half the airflow

DirectAire® uses patent pending technology to angle the air toward the equipment. This means the airflow delivered through the airflow panel is entering the face of the server rack, providing the highest cooling capacity and energy efficiency of any airflow panel on the market. DirectAire® has a 68% open area and a strong durable design that provides superior load performance. DirectAire® is designed for a one-to-one paring with a standard 42U rack.

DirectAire Main View
Previous
Next

Key Performance Characteristics

  • Welded steel grate design
  • 68% open area delivers 2,850 CFM at 0.10" H2O
  • 2,500 lb design load performance
  • Directional airflow
  • Manual and automatic airflow control options

DirectAire®

The elimination of bypass air saves operating expenses in existing facilities and reduces capital expenditures on cooling equipment in new facilities. DirectAire superior load performance is ideal for retrofit and new construction, easily integrating into your existing raised floor system.

Improve Data Center Financial Performance

Directional airflow panels maximize the financial performance of any new or existing data center. The precise delivery of air provides many financial benefits for new and existing facilities.

  • Reduces bypass airflow by over 40% allowing new facilities to reduce the number of CRAH units.
  • Retrofits can set CRAH units with fixed speed fans to standby mode or adjust variable fan drives to operate at a lower static pressure, saving up to 40% in annual fan energy.
  • Improves overall cooling capacity, allowing for the addition of IT equipment without capital investment on infrastructure.

Easily Cool High Density Racks

DirectAire features a 68% open area, capable of delivering 2,850 CFM at .1" H2O static pressure. Each vertical vane has an angle of deflection at the top to direct the airflow toward the server rack, compared to the typical airflow panels which only deliver 30-50% directly to the rack.

Airflow Performance Information

DirectAire® CFM

Pressure
(in. H20)

No Damper
(CFM)

0.02 1250
0.04 1765
0.05 1875
0.06 2050
0.08 2470
0.10 2850

Product Information

Technical Documents
Control Options
Understructure
Brochures

DirectAire Datasheet 24in

DirectAire Detail (PDF) 24in

DirectAire Detail (CAD) 24in

DirectAire Panel 24in BIM

DirectAire Datasheet 60cm

DirectAire Detail (PDF) 60cm

DirectAire Detail (CAD) 60cm

DirectAire Panel 60cm BIM

The DirectAire® is available with these Control options:

DirectAire® is available on the following understructure systems:

Fav Faved

Other Airflow Panel Options

Other Data Center Solutions

More About Tate

Need to talk? We're here for you.

Our team is ready to help you select the best solutions for your project.

Contact our support team
We use cookies on our website www.tateinc.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click “Accept and close” to accept the use of cookies on our website. If you do not click “Accept and close” but continue to use this website: you thereby consent to the use of all Tate cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.