The Multi-Zone Opposed Blade Damper enables individuals responsible for the physical infrastructure to deliver air where the IT user has servers and equipment installed, but restrict airflow delivery into zones where no blanking panels and no equipment is installed. Divided into three zones, (top, middle and bottom) each zone of the manual damper can be adjusted from the surface without removing the Airflow panel for fast, accurate balancing to the fixed IT loads.