60cm System
Performance Chart
The Performance Charts below are divided
into two sections to help you evaluate the overall performance of the
systems. The System Performance Criteria are the most important to consider
because they represent the performance in a typical installation.
SYSTEM
PERFORMANCE CRITERIA
(Tested on Actual Understructure) |
Panel |
U/S | SYSTEM
WEIGHT (per ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT LOADS | Design Loads* | Safety
Factors* (min 2.0) |
10
Passes |
10,000 Passes | All Steel 1000 |
Posilock |
5.5 lbs/ft² |
1000 lbs |
PASS |
400 lbs 181 kg |
400 lbs 181 kg |
150 lbs 68 kg |
All Steel 1250 |
Posilock |
6.5 lbs/ft² |
1250 lbs 567 kg |
PASS |
500 lbs 227 kg |
500 lbs 227 kg |
150 lbs 68 kg |
SYSTEM
PERFORMANCE CRITERIA
(Tested on Actual Understructure) |
|||||||
Panel |
U/S | SYSTEM
WEIGHT (per ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT LOADS | ||
| Design Loads* | Safety
Factors* (min 2.0) |
10
Passes |
10,000 Passes | ||||
All Steel 1000 |
Bolted Stringer |
6.0 lbs/ft² |
1000 lbs |
PASS |
400 lbs 181 kg |
400 lbs 181 kg |
150 lbs 68 kg |
All Steel 1250 |
Bolted Stringer |
7.5 lbs/ft² |
1250 lbs 567 kg |
PASS |
500 lbs 227 kg |
500 lbs 227 kg |
150 lbs 68 kg |
All Steel 1500 |
Bolted Stringer |
8.5 lbs/ft² |
1500 lbs 680 kg |
PASS |
600 lbs 272 kg |
600 lbs 272 kg |
150 lbs 68 kg |
| SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure) |
|||||||
Panel |
U/S | SYSTEM WEIGHT | STATIC
LOADS |
ROLLING
LOADS |
IMPACT LOADS | ||
| Design Loads* | Safety Factors* (min 2.0) |
10 Passes | 10,000 Passes | ||||
Concore 1000 |
Posilock |
8.0 lbs/ft² |
1000 lbs 454 kg |
PASS |
800 lbs 363 kg |
600 lbs 272 kg |
150 lbs 68 kg |
Concore 1250 |
Posilock |
9.5 lbs/ft² |
1250 lbs 567 kg |
PASS |
1000 lbs 454 kg |
800 lbs 363 kg |
150 lbs 68 kg |
| SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure) |
|||||||
Panel |
U/S | SYSTEM
WEIGHT (per ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT LOADS | ||
| Design Loads* | Safety Factors* (min 2.0) |
10 Passes | 10,000 Passes | ||||
Concore 1000 |
Bolted Stringer |
9.0 lbs/ft² |
1000 lbs 454 kg |
PASS |
800 lbs 363 kg |
600 lbs 272 kg |
150 lbs 68 kg |
Concore 1250 |
Bolted Stringer |
10.0 lbs/ft² |
1250 lbs 567 kg |
PASS |
1000 lbs 454 kg |
800 lbs 363 kg |
150 lbs 68 kg |
Concore 1500 |
Bolted Stringer |
11.5 lbs/ft² 51 kg /m² |
1500 lbs 680 kg |
PASS |
1250 lbs 567 kg |
1000 lbs 454 kg |
150 lbs 68 kg |
| Concore 2000 | Bolted Stringer |
12.25 lbs/ft² 59.7 kg /m² |
2000 lbs 907 kg |
PASS |
1500 lbs 680 kg |
1250 lbs 567 kg |
150 lbs 68 kg |
| Concore 2500 | Bolted Stringer |
13.5 lbs/ft² 65.8 kg /m² |
2500 lbs 1132 kg |
PASS |
1500 lbs 680 kg |
2000 lbs 907 kg |
150 68 kg |
*For more information on design load download the Design Load Technical Bulletin. All other tests are conducted under CISCA’s recommended test procedures for access floors.